TRV Thermostatic Radiator Valve Control

DSVT supports the integration of thermostatic radiator valves (TRVs) into its 12-zone heating and cooling system.

This function was primarily developed for Zigbee thermostatic radiator valves integrated into Domoticz, but compatible temperature setpoint devices using other communication technologies can also be supported.

DSVT allows separate TRV devices to be assigned to individual zones. Their target temperatures can be adjusted according to the current heating or cooling demand of each zone.

The controller can take into account the measured room temperature, zone switching thresholds, and the temperature measured by the TRV itself.

1. Why Is Centralised TRV Control Useful?

Conventional thermostatic radiator valves generally regulate heating based on the temperature measured in their immediate surroundings.

However, this temperature may differ from the actual room temperature.

Several factors can affect the TRV's temperature measurement:

DSVT's dynamic control can compensate for these differences by using the temperature measured by a separate sensor assigned to the zone.

This allows TRV operation to respond more accurately to the room's actual heating or cooling requirements.

2. TRV Operating Modes

DSVT provides a dedicated TRV SetPoint selector switch in the Domoticz Switches interface.

The available operating modes are:

In dynamic modes, DSVT can modify the target temperature sent to the valves according to the difference between the measured zone temperature and the switching thresholds.

For TRV control, the zone must have a valid temperature sensor.

3. Using the TRV's Own Temperature Measurement

During dynamic operation, DSVT attempts to retrieve the temperature measured by the TRV itself.

If the valve temperature differs from the room temperature, the controller can apply this difference as additional compensation under certain operating conditions.

For example, if the TRV measures a higher temperature near the radiator than the separate room sensor, DSVT can take this difference into account.

This can reduce the likelihood of the valve closing prematurely while the room has not yet reached the desired temperature.

In the current plugin, the TRV's temperature is retrieved using its Domoticz device identifier.

4. Dynamic TRV Control During Heating

During heating operation, DSVT uses the upper and lower heating switching thresholds of the zone to calculate the TRV target temperature.

The controller may calculate different target values depending on whether the zone's heating demand is active or inactive.

Active Heating Demand

When the zone requires heating, DSVT uses the upper heating switching threshold as the starting point.

The basic compensation formula is:

Compensation = 2 × (Upper Heating Target − Measured Zone Temperature)

The controller rounds the calculated compensation to an integer value.

In dynamic heating mode, DSVT can also compensate for differences between the TRV's own temperature measurement and the zone temperature, particularly when the TRV measures a higher temperature than the room sensor.

The calculation is based on:

TRV Target = Upper Heating Target + Compensation + Applicable TRV Measurement Compensation

Example

The basic compensation is:

2 × (22 − 21) = 2°C

The difference between the TRV and room temperatures is:

22 − 21 = 1°C

The dynamic TRV target temperature becomes:

22 + 2 + 1 = 25°C

This higher setpoint can cause the thermostatic radiator valve to request greater opening through its internal control system.

When Heating Demand Ends

When the room reaches the upper heating switching threshold, or zone operation stops because of another control condition, DSVT can calculate a lower TRV target temperature.

The basic compensation formula is:

Compensation = 2 × (Measured Zone Temperature − Lower Heating Target)

The calculated value may also be adjusted according to the difference between the TRV's own temperature measurement and the zone temperature.

The objective is to make the thermostatic valve reduce heating output when the zone no longer requires additional heat.

5. Heating TRV Setpoint Limits

DSVT limits the dynamic deviation applied to heating TRV target temperatures.

During active heating demand, the calculated TRV target can vary within a maximum range of ±5°C relative to the upper heating target.

When heating demand ends, the lower target sent to the TRV can be reduced by up to 5°C relative to the lower heating target.

The controller rounds these values to 0.5°C increments.

The actual permitted target temperature range may also depend on the limitations imposed by the TRV manufacturer.

6. Dynamic TRV Control During Cooling

By selecting the appropriate operating mode, DSVT can also adjust the target temperatures of thermostatic valve actuators assigned to cooling circuits.

During cooling, the required valve response may differ from conventional radiator heating control.

Therefore, cooling control should only be used with valve actuators whose operating characteristics are suitable for the cooling system.

Target Temperature During Cooling Demand

One of the basic cooling compensation formulas is:

Compensation = 2 × (Measured Zone Temperature − Lower Cooling Target)

DSVT can adjust the target temperature sent to the valve using the cooling switching thresholds and the temperature measured by the TRV itself.

The resulting target temperature influences cooling water flow through the valve's internal regulation.

When Cooling Demand Ends

During cooling operation, the controller can also apply another compensation formula, which uses a multiplier of 6 in the current plugin version.

The calculation is:

Compensation = 6 × (Measured Zone Temperature − Lower Cooling Target)

The difference between the TRV's own measurement and the zone temperature may produce an additional adjustment.

If the room temperature is higher than the temperature measured by the TRV, DSVT can add this positive difference to the calculated target.

Example of Cooling Target Calculation

Consider the following values:

The compensation is:

6 × (24.5 − 24) = 3°C

The difference between the zone and TRV temperatures is:

24.5 − 24 = 0.5°C

The calculated target temperature becomes:

24 + 3 + 0.5 = 27.5°C

The target value actually sent to the TRV also depends on additional limits implemented in the controller and the current switching conditions.

Important: cooling TRV control requires an appropriately designed hydraulic system and compatible valve actuators. Adjusting the TRV target temperature does not replace dew point-based condensation protection.

7. Assigning TRV Devices to Zones

DSVT allows separate TRV devices to be assigned to each of its 12 zones.

Assignment is configured in the plugin's hardware settings using the V_x identifier associated with the relevant zone.

Multiple valves can be assigned to the same zone.

For example, this is useful in rooms with several radiators, each equipped with a separate thermostatic radiator valve.

DSVT can adjust the target temperatures of all valves assigned to a zone according to that zone's current control state.

8. Integration with Zone Control

Thermostatic radiator valve control is an integral part of DSVT's heating and cooling regulation.

Several factors can influence the target temperature sent to a TRV:

When heating or cooling demand ends in a zone, DSVT can adjust the thermostatic valve target according to the appropriate switching state.

Other zones can continue operating independently if they still require heating or cooling.

9. Operating Considerations

For reliable TRV control, the following should be considered:

The target temperature sent to a TRV does not directly represent a valve opening percentage.

The actual valve position is determined by the internal control system of the TRV device.

10. Summary

DSVT supports zone-based thermostatic radiator valve control using different heating and cooling operating modes.

During dynamic operation, the controller calculates the target temperature sent to the TRV according to the zone temperature and switching thresholds.

It can also use the temperature measured by the TRV itself to compensate for local measurement differences.

Heating and cooling control use different compensation formulas, allowing target temperatures to be adjusted according to the operating requirements of each mode.

Properly configured dynamic TRV control can improve the accuracy of zone temperature regulation, reduce the influence of measurement differences caused by radiator valve placement, and contribute to more comfortable and energy-efficient operation.

DSVT – Documentation and Guides

Browse installation instructions, configuration steps and detailed explanations of the control functions.

Heating, Cooling, DHW and Buffer Control – Overview

Overview and principles

Operational logic and operating modes

Intelligent control algorithms

Actuating devices and auxiliary controls

Installation and configuration

Usage and documentation

Version history