Configuration – Step 4: Configuring Temperature Sensors

The fourth step in configuring DSVT is assigning temperature sensors to the appropriate control functions.

DSVT uses the device identifiers (IDX) of temperature sensors available in Domoticz to determine the temperatures of individual rooms, the outdoor environment, the domestic hot water tank, and the water circuits controlled by mixing valves.

Correct temperature sensor configuration is essential for reliable heating, cooling, and domestic hot water control.

1. Temperature Parameter Configuration Interface

Temperature sensor identifiers can be entered in the corresponding parameter field of the DSVT hardware configuration.

The following image shows the configuration field used for temperature-related settings.

DSVT temperature sensor configuration

The configuration consists of keys and their associated values.

Each sensor must be specified using its Domoticz IDX identifier and the appropriate configuration key.

Instead of editing these fields manually, using DSVT's dedicated HTML configuration interface is recommended. This simplifies device selection and assignment.

2. Zone Temperature Sensors

Z_1, Z_2 ... Z_12

DSVT supports up to 12 independent heating and cooling zones.

Zone temperature sensors are identified using the following configuration keys:

Z_1:idx Z_2:idx Z_3:idx ... Z_12:idx

The Z_1 key represents the temperature sensor assigned to the first zone, Z_2 represents the second zone, and so on.

If the installation contains only one controlled zone, using Z_1 is recommended.

At least one valid temperature measurement is required for each active zone.

Using Multiple Sensors in One Zone

DSVT allows multiple temperature sensors to be assigned to the same zone.

In this case, the system can use the arithmetic average of valid sensor readings as the current zone temperature.

For example, with three sensors:

The average temperature is:

(21.5 + 22.0 + 22.5) / 3 = 22.0°C

This can be useful in larger rooms where temperatures vary between different measurement locations.

The same temperature sensor can also be assigned to multiple zones, for example when several independently controlled heating circuits serve the same room.

3. Outdoor Temperature Sensors

K:idx

The K key identifies sensors used to measure outdoor temperature.

K:idx

If multiple outdoor temperature sensors are available, they can also be assigned in the corresponding configuration field.

DSVT can use outdoor temperature measurements for several control functions, including:

The outdoor temperature sensor should preferably be installed in a location where direct sunlight and heat radiated from nearby building structures do not significantly affect its readings.

With appropriate configuration, DSVT can also use outdoor temperature data obtained from online weather services.

4. Domestic Hot Water Tank Temperature

T:idx

The T key identifies the temperature sensor used for the domestic hot water (DHW) tank.

T:idx

DSVT can control domestic hot water production based on the current tank temperature and the configured DHW target temperature.

The temperature sensor allows the system to determine whether additional tank heating is required.

DHW control may also depend on the target temperature, hysteresis, and selected control mode.

If the installation does not include a domestic hot water tank, this sensor assignment can be omitted.

Important: the position of the tank temperature sensor determines which part of the tank is being measured. This is particularly important in stratified hot water storage tanks.

5. Mixing Valve Temperature Sensors

S_1:idx and S_2:idx

DSVT supports the control of two motorised mixing valves.

The temperature sensors associated with these mixing valves are configured using the following keys:

S_1:idx S_2:idx

These keys identify the temperature measurements associated with the water circuits controlled by the first and second mixing valves.

Using temperature feedback, DSVT can control the mixing valve actuator in the required direction.

With an appropriately designed hydraulic system, this makes it possible to regulate different supply water temperatures for underfloor heating and radiator circuits, for example.

The temperature sensor should be installed at an appropriate measurement point in the controlled water circuit so that the feedback accurately reflects the effect of the mixing valve.

6. Mixing Valve Control Slope

S_1M and S_2M

A separate control slope parameter can be configured for each of the two mixing valves.

The corresponding configuration keys are:

S_1M:value S_2M:value

These parameters do not identify temperature sensors. Instead, they contain values associated with mixing valve control.

Adjusting the control slope allows the mixing valve's response to be adapted to the characteristics of the hydraulic system.

Factors to consider include:

An excessively fast control response may cause oscillation, while an excessively slow response may result in delayed tracking of the target temperature.

The appropriate value should be configured through the DSVT HTML interface according to the operating characteristics of the mixing valve.

7. Room Temperature Balancing

L:idx

The L key identifies room temperature sensors used for compensation circulation.

L:idx

The purpose of this function is to reduce temperature differences between rooms.

Temperature measurements from at least two different locations are required.

DSVT determines the highest and lowest temperatures among the valid measurements.

The difference between these two values is compared with the Room max. difference parameter.

If the difference reaches the configured threshold and the controlled heat sources are inactive, the system can activate the circulation pump assigned to compensation circulation.

Calculation Example

The maximum temperature difference is:

24.0 − 21.0 = 3.0°C

If the configured threshold is 2.0°C, the temperature difference condition is satisfied.

Important: this function does not use the average of the sensor readings. Instead, it uses the difference between the highest and lowest measured room temperatures.

8. Rules for Using Multiple Sensors

DSVT can use measurements from multiple temperature sensors for different control functions.

However, the way these measurements are processed depends on the selected function.

Therefore, the same averaging method does not apply to every control function.

9. Verifying Temperature Measurements

After saving the configuration, verify that DSVT correctly recognises the assigned temperature sensors.

Pay particular attention to:

Outdated or incorrect temperature measurements can affect control behaviour.

During initial setup and after configuration changes, checking the Domoticz log is also recommended.

10. Safety Considerations

DSVT performs temperature-based control, making correct sensor assignment essential for reliable operation.

It is particularly important that temperature sensors associated with heat sources, the DHW tank, and mixing valves are installed at the correct physical measurement points.

Sensors used by the controller do not replace the temperature safety sensors and independent overtemperature protection required by the equipment manufacturer.

For radiant cooling systems, reliable relative humidity measurements are also required alongside room temperature measurements to support dew point-based condensation protection.

11. Summary

DSVT temperature configuration is based on assigning the appropriate Domoticz sensor IDX identifiers.

The Z_1–Z_12 keys are used for zones, K for outdoor temperature, T for the DHW tank, S_1 and S_2 for mixing valve temperature sensors, and L for compensation circulation.

Mixing valve control parameters are associated with the S_1M and S_2M keys.

Correct temperature measurements and control parameters allow DSVT to make heating, cooling, and domestic hot water control decisions based on the actual system conditions.

Accurate temperature measurements and correct sensor assignments are among the most important requirements for reliable and energy-efficient DSVT operation.

DSVT – Documentation and Guides

Browse installation instructions, configuration steps and detailed explanations of the control functions.

Heating, Cooling, DHW and Buffer Control – Overview

Overview and principles

Operational logic and operating modes

Intelligent control algorithms

Actuating devices and auxiliary controls

Installation and configuration

Usage and documentation

Version history