The fifth step in configuring DSVT is assigning the switching outputs used for heating and cooling zone valves, motorised mixing valves, and compensation circulation.
DSVT uses switching devices available in Domoticz. During configuration, you can specify which devices receive On or Off commands under different control conditions.
This makes it possible to operate conventional normally closed or normally open valves, bidirectional motorised valves, and various circulation devices.
Switching outputs are assigned through the corresponding parameter fields in the DSVT hardware settings.
The following image shows the settings associated with valve control and compensation circulation.
Switches are assigned using their unique Domoticz device identifiers (IDX).
The corresponding configuration keys determine whether a switch belongs to a particular zone, mixing valve, or compensation function.
The configuration can be edited manually, but using DSVT's dedicated HTML-based setup interface is recommended.
DSVT uses separate parameter fields for assigning switching commands.
Devices assigned to the On field can receive an activation command when the corresponding control condition is met.
For example, this can be used to:
Devices assigned to the Off field can receive a deactivation command when the corresponding control condition is met.
This may be necessary to stop a previously activated relay or in installations where multiple switching outputs must operate in a coordinated manner.
Important: the interpretation of switches assigned to these fields depends on the specific DSVT function. The names of the control fields do not necessarily correspond to the actual mechanically open or closed position of a valve.
DSVT supports up to 12 independent heating and cooling zones.
Switching devices assigned to individual zones are identified using the following configuration keys:
Z_1:idx Z_2:idx Z_3:idx ... Z_12:idx
The Z_1 key identifies the switching output assigned to the first zone, Z_2 identifies the second zone, and so on.
Zone switching is determined by the measured room temperature, configured temperature targets, hysteresis, and current heating or cooling demand.
Each zone can operate independently, allowing DSVT to request switching only for zones where the relevant control conditions are satisfied.
Multiple switching outputs can be assigned to a single zone.
This can be useful when a room contains several separate heating circuits that should operate according to the same temperature control requirements.
The device identifiers must be entered using the format required by the corresponding configuration field.
Before assigning the same physical switch to multiple independent control functions, verify that the commands will not conflict.
Zone valves used in heating and cooling systems may have different operating characteristics.
A normally closed valve typically opens when the appropriate electrical control signal is applied.
When electrical power is removed, the valve returns to its normally closed position.
This arrangement is common with thermoelectric zone valve actuators.
A normally open valve remains open when no electrical control signal is applied.
When activated, the actuator can move the valve towards its closed position.
With this arrangement, it is particularly important that the control commands match the actual operating logic of the valve.
Important: the NC and NO designations describe the valve's default mechanical position. They must not automatically be interpreted as equivalent to the On and Off states of a Domoticz switch.
Simple zone valves generally require only one switching output.
The controller activates or deactivates the corresponding relay, and the valve opens or closes according to its own operating mechanism.
Examples include:
In the DSVT configuration, the switch must be assigned to the appropriate zone and switching function.
If the valve does not require separate electrical commands for opening and closing, two physical control outputs are not necessary.
Some motorised valves require separate electrical control signals for opening and closing.
In these cases, two switching outputs may be required:
Correct assignment of these outputs is essential.
An incorrect configuration may cause the valve to move in the opposite direction or operate improperly.
Important: simultaneous activation of the opening and closing outputs must also be prevented through appropriate electrical interlocking. Safety interlocking should not rely solely on software timing.
DSVT supports two separate motorised mixing valves.
The corresponding switching outputs can be assigned to the first and second mixing valves using the appropriate configuration keys.
S_1:idx S_2:idx
The purpose of mixing valve control is to maintain the desired supply water temperature in the controlled circuit.
DSVT uses feedback from the assigned temperature sensors to determine the required control direction.
For bidirectional actuators, the opening and closing outputs must be specified in their respective configuration fields.
Actual mixing valve operation also depends on the actuator type, electrical wiring, and hydraulic system design.
DSVT can use timed switching commands to operate mixing valves.
With pulsed control, the actuator does not necessarily travel from one end position to the other during each control cycle.
Instead, the system can adjust the valve position through shorter control pulses.
This allows gradual regulation, particularly in systems where the supply water temperature changes slowly.
The following factors should be considered:
Excessively long pulses may cause overshooting, while excessively short pulses may result in slow or unreliable control.
Domoticz switching devices may provide a delayed switch-off option.
This can be particularly useful for motorised valve control where an output should remain active for only a specified period.
Appropriate timing determines how long a switching output remains active following a control command.
For pulsed mixing valve control, the timing must correspond to the DSVT control algorithm and the operating characteristics of the actuator.
Important: delayed switch-off does not replace electrical interlocking between the two motor directions and must not be considered an independent safety mechanism.
Separate control parameters can be configured for the first and second mixing valves.
These are identified by the following keys:
S_1M:value S_2M:value
These fields contain mixing valve control parameters rather than Domoticz device identifiers.
When selecting appropriate values, the thermal inertia of the system, actuator speed, and DSVT update interval must be considered.
The DSVT operating parameters include a configurable update interval, which may be set to 5 minutes, for example.
The exact effect of each parameter depends on the control algorithm implemented in the DSVT version being used.
Mixing valve fine-tuning should preferably be performed under actual operating conditions while monitoring changes in supply water temperature.
One or more switching devices can be assigned to the DSVT compensation circulation function.
The corresponding configuration key is:
L:idx
The purpose of compensation circulation is to reduce temperature differences between rooms by redistributing available thermal energy.
This function uses separately assigned room temperature sensors to determine the highest and lowest room temperatures.
When the temperature difference reaches the configured threshold and the controlled heat sources are inactive, the system can activate compensation circulation.
Switching outputs can be configured using the On and Off fields associated with this function.
For example, the assigned switches may operate relays controlling a circulation pump.
Important: the L switching configuration used for compensation circulation and the L temperature sensor assignment described in the previous configuration step are located in separate parameter fields and must not be confused.
Before saving the DSVT configuration, each assigned switching device should be tested individually.
Verify the following:
If a switch operates the wrong equipment, check its IDX identifier and physical wiring.
Testing must always be performed in accordance with the equipment's operating and safety requirements.
Controlling motorised valves and circulation pumps can directly affect the hydraulic operation of heating and cooling systems.
Particular attention must therefore be paid to safe operation during configuration.
Important: DSVT does not replace the equipment's own electrical, hydraulic, or thermal safety systems.
The fifth step in configuring DSVT is assigning the switching outputs for zone valves, two motorised mixing valves, and compensation circulation.
Switching devices are assigned to the appropriate functions using configuration keys and Domoticz IDX identifiers.
The system supports conventional On/Off switching, motorised valves with separate opening and closing controls, and timed pulsed valve operation.
Compensation circulation can be controlled through separate switching outputs according to the temperature difference between rooms.
Correct assignment and configuration of valves, motorised actuators, and circulation pumps are essential for accurate, reliable, and safe DSVT heating and cooling control.