Operating Mode: Buffer Tank Control

DSVT supports automatic temperature control of buffer tanks connected to heating and cooling systems. A buffer tank makes it possible to temporarily store thermal energy, which can later be used to heat or cool the building.

This can be particularly beneficial in heat pump installations and in buildings where surplus solar energy or electricity at a lower cost is available during certain periods.

DSVT buffer tank control can take into account the current tank temperature, configured target temperature, hysteresis, outdoor temperature, and available energy metering data.

1. Buffer Tank Temperature Control

Buffer tank regulation is based on the temperature measured by a sensor installed in the tank.

DSVT provides separate target temperatures and hysteresis settings for heating and cooling operation.

Depending on the selected operating mode and the current tank temperature, the controller starts or stops the configured heat sources.

Proper hysteresis settings can reduce excessive switching and help adapt control behaviour to the buffer tank volume, heat source capacity, and thermal inertia of the system.

2. Controlling Two Heat Sources

DSVT buffer tank control also supports two separate heat sources.

These may include heat pumps, boilers, or other compatible heating and cooling equipment.

Separate heat source selectors are available for buffer tank heating and cooling control.

Available operating modes include:

The available control modes may differ between heating and cooling operation.

Heat source switching can be based on buffer tank temperature, outdoor temperature, or outdoor dew point in the applicable operating modes.

Simultaneous operation of two heat sources must only be enabled in hydraulic and electrical installations specifically designed to support it safely.

3. Outdoor Temperature-Dependent Target Temperature

The buffer tank target temperature can be adjusted automatically according to outdoor temperature.

This is particularly useful for air-to-water heat pump systems, as their efficiency and available heating capacity also depend on outdoor temperature.

Heating Operation

During heating operation, a standard target temperature and a higher target value can be configured. The controller may apply the higher temperature when outdoor conditions are more favourable.

For example:

In this example, the controller can heat the buffer tank to a higher target temperature when the configured outdoor temperature conditions are satisfied.

This allows the heat pump to store additional thermal energy during more favourable daytime conditions, which can then be used during colder periods.

Important: a higher storage temperature increases the required supply water temperature, which can reduce the heat pump's coefficient of performance (COP). The approach is beneficial only if the savings resulting from more favourable outdoor conditions exceed the additional energy losses associated with higher-temperature storage.

Cooling Operation

During cooling, the same principle can be applied in reverse. When outdoor temperatures are lower, the system may produce and store colder water in the buffer tank.

The stored cooling energy can then be used later, for example during warmer daytime hours.

The potential energy savings depend on the cooling equipment's efficiency, tank insulation, stored water temperature, and the building's cooling demand.

When defining cooling target temperatures, particular attention must be paid to condensation prevention and the correct design of the connected cooling circuits.

4. Weather Forecast-Based Control

DSVT can adjust the buffer tank target temperature using more than a fixed outdoor temperature threshold.

In the appropriate operating mode, available weather forecast data can also be used to identify periods that are more favourable for heating or cooling.

The configuration provides automatic operating periods based on the warmest or coldest hours of the daily forecast.

During heating operation, the controller can favour the warmest forecast hours, while during cooling it can favour the coldest hours.

This makes it possible to schedule energy production during periods when the heat pump is expected to operate more efficiently.

Forecast-based operation requires valid weather data and properly configured temperature parameters.

5. Using Surplus Solar Energy

DSVT can also adjust the buffer tank target temperature according to surplus energy available from a solar photovoltaic system.

This requires suitable energy metering data, such as measurements from a grid power meter or a P1 meter integrated into Domoticz.

One example is the HomeWizard P1 meter.

When the configured solar power threshold is reached, the controller can apply a separate target temperature and hysteresis setting.

Solar Energy Control During Heating

During heating operation, the system can use available surplus solar energy to heat the buffer tank to a higher target temperature.

For example, the normal target temperature of 40°C can be increased to 45°C when the configured surplus solar power condition is satisfied.

In this way, some of the available surplus electricity can be stored as thermal energy.

Solar Energy Control During Cooling

During cooling operation, surplus solar energy can also be used to produce colder buffer water.

When the configured conditions are satisfied, the system can apply a target temperature lower than the normal cooling setpoint.

The stored cooling energy may subsequently reduce the operating demand of the cooling equipment.

The purpose of solar-based control is not necessarily to minimise instantaneous electricity consumption, but to make better use of available surplus energy by storing it for later use.

6. The Role of Buffer Tank Hysteresis

Choosing an appropriate hysteresis value is important for both buffer tank regulation and heat source operation.

Hysteresis that is too small can result in frequent heat source switching, while an excessively large value can cause greater fluctuations in tank temperature.

DSVT provides separate hysteresis settings for:

This allows the controller to adapt to different operating conditions.

When selecting suitable values, the tank volume, heat source capacity, required temperature range, and desired switching frequency should all be considered.

7. Energy Storage Capacity of a Buffer Tank

Water is well suited to thermal energy storage because of its relatively high specific heat capacity.

The amount of energy that can be stored in a buffer tank depends on the water volume and the usable temperature difference.

An approximate calculation is:

Stored energy (kWh) = water volume (litres) × temperature difference (°C) × 0.001163

For example, with a 500-litre buffer tank and a temperature difference of 5°C:

500 × 5 × 0.001163 = 2.91 kWh

This means that, under ideal conditions, the tank can store approximately 2.9 kWh of thermal energy within the specified temperature range.

The amount of energy that can actually be used is also affected by tank heat losses, water stratification, and the operating conditions of the connected heating or cooling system.

A buffer tank is therefore suitable for short-term energy storage and shifting thermal energy production to a different time, although its storage capacity is limited by tank volume and the available temperature difference.

8. Heat Pump Efficiency and Buffer Tank Control

The efficiency of air-to-water heat pumps depends significantly on outdoor temperature and the required supply water temperature.

The coefficient of performance (COP) indicates how much thermal energy a heat pump produces per unit of electrical energy consumed.

For example:

These are illustrative values and do not represent universal COP figures for specific outdoor temperatures.

The actual COP must be evaluated using the manufacturer's performance data and the relevant operating conditions.

Intelligent buffer tank control can make it possible for the heat pump to produce more energy during periods of more favourable operating conditions.

However, storing heating water at a higher temperature, or cooling water at a lower temperature, may itself require additional energy. Therefore, the efficiency of the entire system must be considered.

9. Hydraulic Design and Safety Considerations

Efficient buffer tank operation requires an appropriate hydraulic configuration.

The design must take into account tank volume, circulation pumps, mixing valves, the permitted operating ranges of the heat sources, and the required safety devices.

During cooling operation, condensation protection, appropriate pipe insulation, and dew point considerations are particularly important.

DSVT software control does not replace the heat sources' built-in frost protection, overtemperature protection, pressure protection, or other safety functions.

10. Summary

DSVT buffer tank control provides several energy efficiency features beyond conventional target temperature regulation.

Operation based on outdoor temperature, weather forecasts, and surplus solar energy allows thermal energy production and consumption to be coordinated over time.

Support for two heat sources, separate heating and cooling parameters, and configurable hysteresis allows buffer tank operation to be adapted to the specific building services installation.

Properly configured buffer tank control can contribute to more economical heat pump operation, better use of available solar energy, and more balanced heating and cooling system performance.

DSVT – Documentation and Guides

Browse installation instructions, configuration steps and detailed explanations of the control functions.

Heating, Cooling, DHW and Buffer Control – Overview

Overview and principles

Operational logic and operating modes

Intelligent control algorithms

Actuating devices and auxiliary controls

Installation and configuration

Usage and documentation

Version history