In addition to heating and cooling control, DSVT can also manage domestic hot water (DHW) production. DHW control can operate independently or alongside heating, cooling, and buffer tank control.
The DHW control interface is similar in several respects to the heating and cooling thermostat settings. However, the fundamental control principle is different.
While space heating and cooling are regulated according to indoor temperature measurements, DHW control primarily uses the measured hot water tank temperature and the configured target temperature.
DSVT can manage two separate DHW heat sources and provides several automatic heat source selection options.
The controller continuously monitors the DHW tank temperature and compares it with the configured target value.
When the appropriate control conditions are met, it starts or stops the equipment assigned to domestic hot water production.
Operation is influenced by several settings, including:
A properly configured temperature sensor is required to measure the tank temperature.
DSVT can control two separate devices for domestic hot water production. These may include a heat pump, boiler, electric immersion heater, or other compatible heat-producing equipment.
The DHW thermostat offers several operating modes.
The system uses only the first DHW heat source.
The system uses only the second DHW heat source.
The system selects between the two DHW heat sources according to the configured conditions.
Switching can be based on factors such as tank temperature, outdoor temperature, or outdoor dew point.
In Dual mode, the second heat source can supplement the operation of the first when necessary.
Activation conditions are determined by the selected control mode, the DHW target temperature, and the configured temperature difference settings.
Using a second heat source can be particularly beneficial when the capacity of the primary device is insufficient to maintain the required hot water temperature under certain operating conditions.
When DSVT controls space heating, cooling, or a buffer tank in addition to DHW production, it is important to define the order in which different thermal demands are served.
The DHW priority setting allows domestic hot water production to take precedence over other control functions.
This is particularly important when DHW production and space heating share the same heat source or hydraulic components.
In this configuration, DHW control does not impose a separate priority restriction on the heat sources assigned to heating, cooling, or buffer tank control.
However, the operation of the different systems may still be affected by shared switches, hydraulic arrangements, and other control conditions.
With this setting, the system coordinates the operation of DHW and heating/cooling heat sources.
During DHW production, the configured priority rules can prevent simultaneous operation of heating or cooling switches associated with the same heat source.
This helps prevent a single heat-generating device from being required to perform two incompatible functions at the same time.
In this configuration, the selected priority rules apply between DHW production and buffer tank control.
The controller manages primary and secondary heat sources according to the configured relationships.
In complex installations, DHW priority can be applied simultaneously over heating/cooling and buffer tank control.
This is useful when all three control functions share some or all of the same heat sources.
DSVT also provides timed operating options for priority control.
The following durations can be assigned to the selected priority relationship:
Timed priority control alternates priority states according to the configured intervals, allowing other thermal demands to receive attention rather than remaining indefinitely postponed.
This can be particularly useful with larger DHW tanks, limited heat generation capacity, or systems serving multiple thermal loads.
Important: priority control applies to the appropriately configured heat source switches. It does not replace hydraulic diverter valves, check valves, or the built-in safety controls of the heat-generating equipment.
DSVT can also be used to control domestic hot water production with an electric immersion heater.
The electric immersion heater can be configured as a separate switching device, for example as the second DHW heat source.
DHW control includes an outdoor temperature threshold associated with the activation conditions of the second device.
In an appropriate heat source selection mode, this threshold can be used to switch to an alternative DHW heating device when the outdoor temperature falls below a configured level.
This can be particularly useful in heat pump installations where low outdoor temperatures reduce the efficiency or available heating capacity of the heat pump.
However, using an electric immersion heater is not necessarily more economical. The switching threshold should be determined according to the actual performance of the equipment and current energy costs.
For safety, electric immersion heaters must have appropriate overtemperature protection, electrical protection, and thermostatic safety devices in accordance with the manufacturer's specifications.
DHW control can use separate hysteresis and Dual temperature difference settings to determine heat source switching conditions.
Hysteresis helps prevent minor changes in tank temperature or fluctuations in external conditions from causing excessively frequent heat source switching.
The Dual temperature difference influences the temperature deviation required to activate the second DHW heat source in the selected operating mode.
Averaging tank temperature readings can also help reduce the effects of short-term measurement fluctuations.
Appropriate settings depend on the tank capacity, thermal losses, hot water demand, and the heating capacity of the connected devices.
DSVT can be adapted to DHW systems with different hydraulic configurations.
With a suitable installation, possible arrangements include:
The range of feasible configurations is primarily determined by the hydraulic design, valves, circulation pumps, and the control capabilities of the heat-generating equipment.
The selected installation must prevent unwanted water circulation or heat transfer between different hydraulic circuits.
In domestic hot water production, energy efficiency must be balanced with appropriate hygiene and safety requirements.
The operating temperature of the DHW tank and any necessary hygiene-related heating cycles must be determined according to the system design, the tank manufacturer's instructions, and applicable requirements.
DSVT temperature control alone does not replace the water temperatures, operating procedures, and safety measures required to manage the risk of Legionella growth.
Excessively high domestic hot water temperatures can cause scalding. Where appropriate, a thermostatic mixing valve should be installed to limit the delivered water temperature.
DSVT DHW control can be used as a standalone domestic hot water controller or as part of a more comprehensive building services control system.
Support for two heat sources, automatic switching options, and configurable priority rules allows the controller to adapt to a wide range of heating and hot water installations.
Properly configured temperature, heat source switching, and priority settings can contribute to reliable domestic hot water supply and more efficient use of the available energy sources.