Open Window-Based Zone Control

DSVT allows heating and cooling zones to be controlled automatically according to the open or closed state of windows and doors.

The purpose of this function is to prevent unnecessary heating or cooling while a room is being ventilated, thereby reducing energy consumption.

Open window detection operates independently for each zone, so ventilating a single room does not automatically disable heating or cooling throughout the entire building.

1. Assigning Window and Door Sensors

DSVT supports assigning window and door opening sensors to each of its 12 heating and cooling zones.

Sensors can be configured in the plugin's Hardware Settings interface using the corresponding W_x field for each zone.

Multiple sensors can be assigned to a single zone, allowing windows and doors within the same room to jointly influence zone operation.

For example, two windows and a patio door in a living room can all be assigned to the same heating and cooling zone.

2. How Open Window Detection Works

The controller monitors the states of configured sensors as reported by Domoticz.

The following states are interpreted as open:

If a sensor assigned to a particular zone reports an open state, DSVT disables the heating or cooling demand for that zone.

As a result, the system:

This is particularly useful in multi-zone systems where individual rooms can be heated or cooled independently.

3. Multiple Window Sensors in One Zone

The intended behaviour is that when several opening sensors are assigned to one zone, an open state reported by any one of them is sufficient to disable heating or cooling for that zone.

For example, consider a living room with three sensors:

In this situation, heating or cooling should be suspended because at least one opening is detected as open.

Normal zone control can resume when all assigned opening sensors report a closed state.

4. Automatic Resumption of Zone Control

After the window or door is closed, DSVT allows normal temperature regulation for the affected zone to resume.

This does not necessarily mean that heating or cooling will start immediately.

The controller evaluates the current room temperature, configured target temperature, and switching hysteresis again.

If the zone still requires heating or cooling, the corresponding zone control can be reactivated.

If the room temperature is already within the required range, the zone remains inactive.

5. What Happens If a Sensor Becomes Unavailable?

DSVT reads sensor states from Domoticz device data.

If a configured sensor is missing from the available device data, the plugin may be unable to determine its actual physical state.

Window states are initially treated as closed. Consequently, if a sensor is missing or its state is not being updated correctly, heating or cooling for the zone may remain enabled.

The advantage of this approach is that a depleted sensor battery or communication failure does not necessarily prevent the room from being heated.

However, the controller may fail to detect a window that is physically open.

Important: sensor operation and battery condition should therefore be checked regularly. Open window detection is an energy management feature, not a security alarm system.

6. Displaying Window Status in Domoticz

DSVT creates a separate text status device for each zone to display the current state of open window control.

The display distinguishes between two main states:

The status indicators for all 12 zones allow users to check which rooms currently have an open window or door reported by the sensors.

DSVT zone control panel and window status indicators

7. Impact on the Overall Heating and Cooling System

Open window detection primarily affects the control of the corresponding zone.

If other zones still require heating or cooling, they can continue operating.

However, if heating or cooling demand disappears from all active zones, DSVT's overall control logic may also adjust the operation of the heat sources.

Open window detection can therefore indirectly influence the energy consumption of the entire system.

8. Summary

DSVT open window-based zone control automatically suspends heating or cooling in affected rooms during ventilation.

The function can be configured independently for every zone, supports multiple window and door opening sensors, and provides status information through the Domoticz interface.

Properly configured open window detection can reduce unnecessary energy consumption during ventilation while allowing unaffected zones to continue operating normally.

DSVT – Documentation and Guides

Browse installation instructions, configuration steps and detailed explanations of the control functions.

Heating, Cooling, DHW and Buffer Control – Overview

Overview and principles

Operational logic and operating modes

Intelligent control algorithms

Actuating devices and auxiliary controls

Installation and configuration

Usage and documentation

Version history